63210.167.WH1 # 63210 | A jax FireProtect 2 RB (Heat/CO) Jeweller white is a wireless fire detector designed to provide advanced protection against dangerous overheating and carbon monoxide in residential and professional environments. The device integrates high-precision A1R heat sensors and a chemical carbon monoxide sensor with a lifespan of up to 10 years , ensuring fast and reliable detection even in the absence of smoke. Long-range Jeweller radio communication up to 1700 m , intelligent interconnected fire alarms and a built-in 85 dB siren ensure immediate and coordinated notifications. The elegant black design, long-life replaceable battery , continuous self-diagnosis and quick installation make the device ideal for advanced and easily manageable security systems. Ajax
referencia : 63210.167.WH1
brand : Ajax Systems
EAN: 4823114040252
Disponibilità: 1
LIQUIDACION TOTAL ×
CLEARANCE SALE!
Take advantage of our must-see outing offers.
Discover the promo >>
63210.167.WH1 | WIRELESS HEAT AND CO DETECTOR WITH REPLACEABLE BATTERIES

The Ajax FireProtect 2 RB (Heat/CO) Jeweler, 63210.167.WH1, white, is a wireless fire detector designed to provide reliable, continuous protection against dangerous overheating and carbon monoxide in residential and commercial environments. The device combines next-generation sensors with advanced radio communication, ensuring rapid detection, reduced false alarms, and immediate notifications. The elegant black design easily integrates into any environment, while constant self-diagnosis, interconnected alarms, and long-lasting replaceable batteries make management simple and safe over time.
Main specifications:
- A1R high precision heat sensors for dangerous temperature detection
- Chemical carbon monoxide sensor with operating life of up to 10 years
- Two-way Jeweler radio communication with a range of up to 1700 m
- Intelligent interconnected fire alarms with built-in 85 dB siren
- Long-life replaceable CR123A batteries with continuous monitoring
- Automatic self-diagnosis and quick installation with SmartBracket support
Further details
Technical data sheet
| 63210.167.WH1 | |
| Communication | |
| Jeweler communication technology | Proprietary wireless communication technology to transmit commands, alarms, and events. Key features:
|
| Radio frequency bands | 866.0 - 866.5 MHz 868.0 - 868.6 MHz 868.7 - 869.2 MHz 905.0 - 926.5 MHz 915.85 - 926.5 MHz 921.0 - 922.0 MHz Depence on the sales reaction |
| Maximum effective radiated power (ERP) | up to 20 mW Automatic power control to reduce power consumption and radio interference. |
| Radio signal modulation | GFSK |
| Radio signal range | Up to 1,700 m up to 5,500 ft Between the detector and a hub (or radio signal range extender) in an open space. |
| Encrypted radio communication | All the data stored and transmitted are protected by block encryption featuring a dynamic key. |
| Frequency hopping | To prevent radio interference and jamming |
| Sensitive elements | heat sensor CO (carbon monoxide) sensor |
| Dangerous temperature detection | |
| Sensitive element | according to the requirements for Class A1R heat detectors Requirements of EN 54-5 and BS 5446-2 standards |
| High temperature alarm | at temperatures above 64 °C at temperatures above 147 °F |
| Temperature spike alarm | when the temperature rises more than 10°C 50°F in 1 minute or less |
| Carbon monoxide (CO) detection | |
| Sensitive element | chemical CO sensor |
| Alarm if accumulated dose of CO is exceeded | more than 50 ppm (0.005%) — no more than in 90 minutes more than 100 ppm (0.01%) — no more than in 40 minutes more than 300 ppm (0.03%) — no more than in 3 minutes CO concentration of 400 ppm (0.04%) within 3 hours can be life-threatening. The detector stops notifying about the dangerous level of carbon monoxide when the concentration drops to 50 ppm (0.005%) within one minute. |
| Sensor life | 10 years After 10 years of operation, the detector must be replaced with a new one. |
| Additional features | |
| Built-in siren | 85 dB volume at a distance of 3 meters 85 dB volume at a distance of 9 ft Sound notification of alarms. Active until the reason for triggering is eliminated or until the user disables the notification. |
| Interconnected fire detectors alarm | via primary interconnection If one of the fire detectors in the system detects a threat, it sends an alarm to the hub. Within 20 seconds, the hub initiates an interconnected alarm and sends data to Ajax apps. via fallback interconnection1 At the same time with notifying the hub, the initiating detector sends an alarm directly to other detectors. All connected detectors activate the buzzer within a minute. It will work even in the worst-case scenario of losing connection with the hub. 1 Fallback interconnected alarm is available only for FireProtect 2 detectors with firmware version 5.59.2.ХХ or later. Devices that support the fallback interconnected alarm are marked on the package with a “Fallback interconnect supported” label. |
| LED indication | green is a power indication A LED indicator on the device enclosure lights up once every 56 seconds. The indication meets the requirements of EN 50291 yellow is an indication of malfunctions A LED indicator on the device enclosure lights up when malfunctions are detected. For example, in the case of discharged batteries, contamination of the smoke chamber, or end of the service life red is an indication of fire alarms A LED indicator on the device enclosure lights up when the detector registers a fire alarm |
| Button on the front panel of the detector | In normal mode, when pressed, it starts the smoke chamber test. In the event of an alarm or malfunction, pressing turns off the detector sound notification. |
| Recommendations | The device is designed only for indoor installation SmartBracket mounting panel allows adjusting the position of the detector after installation. |
| Sabotage protection | |
| Tampering alarm | Alerts of attempts to detach the detector from the surface or remove the mounting panel. |
| Protection against spoofing | device authentication |
| Detection of communication failure | within 15 minutes The time to detect communication loss depends on the settings for the number of undelivered data packages (specified in the Jeweler or Jeweller/Fibra settings). The polling interval is fixed at 300 seconds. |
| Power supply | |
| For FireProtect 2 RB (Heat/CO) | 2 × CR123A batteries Up to 7 years of battery life. |
| Enclosure | |
| Color | White |
| Dimension | 124 × 124 × 45 mm 4.88″ × 4.88″ × 1.77″ |
| Weight | 270 g 9.52 oz |
| Operating temperature range | from 0 °C to +50 °C from 32°F to 122°F |
| Operating humidity | up to 80% |
| Protection class | IP20 |
| Complete set | FireProtect 2 RB (Heat/CO) Jeweller SmartBracket mounting panel Installation kit 2 × CR123A battery (pre-installed) Quick start guide |
| Warranty | 24 months |